3-4SectionWiring and Connections
22
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in
the following diagram.
200 mm min.
Metal plate (iron)
CompoBus/S
transmission lines
Control cables and
SRM1 power lines
Power cables
Conduit
Separate the CompoBus/S transmission lines, power and control lines, and
power cables, as shown in the following diagram.
CompoBus/S
transmission lines
Control cables and
SRM1 power lines
Power cables
Terminal Connections Always use crimp connectors for the SRM1s power lines and transmission
lines.
Use M3 terminal screws and tighten the screws securely (to a torque of
0.48 N S m).
Recommended Terminals: Use the terminals shown below.
Fork terminal
Round terminal
6.0 mm max. 6.0 mm max.
Vedere la pagina 31