
USER’S MANUALMODEL 3G3FV-PDRT1-SIN(For SYSDRIVE 3G3FV High-function General-purpose Inverters)CompoBus/D (DeviceNet)Communications CardCat. No. I525-E
1-4H Applicable to Various System ConfigurationsRemote I/O communications and message communications are available as communications func-tions. Norma
5-38D Error CodesCode Display Content01 PUF Fuse open02 UV1 Undervoltage (main)03 UV2 Undervoltage (CTL)04 UV3 Undervoltage (MC)05 SC Short-circuit06
5-395-4-5 Parameter Constant Reading and WritingThe following tables show the SYSDRIVE 3G3FV-series Inverter parameter constant numbers and thecorresp
5-40Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-41D Tuning (C) Parameter ConstantsConstant Name Regis- Setting Setting Default ChangControl mode settingter No. unit range setting es dur-ing op-era
5-42Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-43D Command-related (d) Parameter ConstantsConstant Name Regis- Setting Setting Default ChangControl mode settingter No. unit range setting es dur-i
5-44Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-45Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-46D Option (F) Parameter ConstantsConstant Name Regis- Setting Setting Default ChangControl mode settingter No. unit range setting es dur-ing op-era
5-47Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
1-51-2 CompoBus/D FeaturesH System Configuration ExampleOMRON Master UnitMaster by other companyOMRON Master UnitOMRON ConfiguratorOMRON ConfiguratorC
5-48Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-49Constant Control mode settingChanges dur-ing op-erationDefaultsettingSettingrangeSettingunitRegis-ter No.NameConstantFluxvectorOpenloopvectorV/f w
5-50Note 1. The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4 kWInverter will be displayed.Note 2. These are valu
Chapter 6Communications Errors6-1 Communications Line Errors6-2 Message Communications Errors6-3 Special Remote I/O Errors6-4 Inverter Faults6
6-26-1 Communications Line ErrorsMalfunctions in CompoBus/D communications that are a result of broken wires, short circuits, reversedwiring, duplicat
6-3Indicator CountermeasuresMeaningDisplayIndicator CountermeasuresMeaningStatusColorNS GreenLit The CompoBus/D Network (DeviceNet) isoperating normal
6-4Indicator CountermeasuresMeaningDisplayIndicator CountermeasuresMeaningStatusColorWDGreen Flashing The CPU Unit of the Card is operating nor-mally.
6-56-2 Message Communications ErrorsH Explicit Message ErrorsIf an explicit message is sent, but communications do not end normally, one of the follow
6-66-3 Special Remote I/O ErrorsH Special Remote I/O ErrorsIf each function is not set properly using the special remote I/O, the MSB of the function
6-76-4 Inverter FaultsH Detecting Inverter FaultsWhen a fault is detected in the Inverter itself, the status will change as shown in the following tab
1-6H Free Remote I/O AllocationA Configurator (sold separately) can be used to enable flexible allocation of I/O, i.e., in any area and inany order. T
Chapter 7CommunicationsPrograms (SYSMAC C200HX/HG/HE PCs)7-1 Standard Remote I/O Programming7-2 Message Communications Programming7-3 Special Remote I
7-2Note In this chapter, the bits, words, and data memory used in the ladder pro-grams are selected at random. When creating actual programs, modify t
7-3H Timing Chart00000 (Frequency Reference Input Bit)00001 (Forward Input Bit)00002 (Reverse Input Bit)Word m bit 2(During Forward Run)Word m bit 3(D
7-4H Ladder ProgramForward/Stop Bit(word n bit 0)Reverse/Stop Bit(word n bit 1)Fault Flag(03000)Fault Reset Input Bit(word n bit 2)Reverse Operation 0
7-57-2 Message Communications Programming7-2-1 Inverter Fault ProcessingThe message communications programming example given here reads and stores the
7-6H Timing ChartWord m bit 0 (Fault Bit)00000 (Fault Read Flag)03003 (Sending Message Flag)03002 (Message Sent Flag)IOWR instruction execution00001 (
7-7H Ladder ProgramMaster Unit: Node 0DIFU (013)03001MOVD (083)DM0000#0210DM0300MOV (021)#0000DM0300Fault BitFault Bit 0300000100 (Reset Input Bit)ORW
7-8CMP (020)#0000DM2001000020000010112Message Communications Enabled FlagMOV (021)DM2001DM010025506 (Equals Flag)MOV (021)DM2004DM02000000003003IOWR (
7-9H AllocationsBitBitBitBitBitBit010000000000001000020300003001Program Start Input BitMessage Execution FlagCommand Write FlagResponse FlagSending Me
7-10H Timing Chart01000 (Program Start Input Bit)01001 (Start Switch ON)00000 (Message Execution Flag)03000 (Sending Message Flag)03001 (Message Sent
1-71-3 CompoBus/D System Configuration1-3-1 System ConfigurationCompoBus/D is a multi-bit, multi-vendor network that combines controls and data on a m
7-11H Ladder Program01000 (Program Start Input Bit)CMP (020)#0000DM0201BCD (024)DM0200DM0202BSET (071)#0000DM0200DM0220DIFU (013)01001DVB (053)DM0002#
7-12Master Unit: Node 001001MOV (021)#D000DM1001MOV (021)#00FEDM0500MOV (021)#8207DM1000MOV (021)DM0002DM1003MOV (021)#0064DM1002MOV (021)#2801DM1004M
7-137-3 Special Remote I/O Programs7-3-1 Simple Operation ProgramsThis section describes examples of simple operation programming using special remote
7-14D Program-related Bits UsedWord Function00000 Program Start Input Bit00001 Program End Input Bit00002 Program Execution Flag00003 Communications E
7-15H Timing Chart00000 (Program Start Input Bit)00001 (Program End Input Bit) or03110 (Communications Error Flag)00002 (Program Execution Flag)00100
7-164. When the Inverter Status Read Flag is turned ON, the Inverter status will be read. When the InverterStatus Read Completed Flag is turned ON, th
7-17H Ladder Program00000DIFU (013)03000MOV (021)#0010DM0100MOV (021)#0001001MOV (021)#0000DM0101MOV (021)#0003DM0100MOV (021)#0021DM01010010003100255
7-180310303105CMP (020)#0003m00102ANDW (034)m+1#00FFDM1002CMP (020)#00021DM100203106ASL (025)00100302003010310403105 03106ANDW (034)m+1#FF00DM1003ANDW
7-19MOV (021)#000000100004MOV (021)#0010DM0100MOV (021)#0000DM0101MOV (021)#0000DM0102XFER (070)#0002DM0100nMOVD (083)DM0102#0010n+2Executes stop comm
7-20D Remote I/O Allocation AreasI/O classification Word 15 to 8 7 to 0Output(PC to 3G3FVn Register number (leftmostbyte)Function code (10: Write, 03:
1-8H Free Allocation: Configuration with a ConfiguratorSlaveSlaveSlave3G3FV-PDRT1-SIN CompoBus/D Communications CardSYSMAC DRIVE 3G3FV InverterC200HW-
7-21H Ladder Program00000 (Read Parameter Input Bit)DIFU (013)00001CMP (020)DM0205mCMP (020)DM0206DM0208030000300100001ANDW (034)DM0000#FF00DM0200ORW
7-227-3-3 Writing Parameter DataThis programming example is designed to write the parameter data in the 3G3FV Inverter. After writinghas been complete
7-23H Timing Chart1. 2. 3. 4.00000 (Write Parameter Input Bit)03000 (Data Write Flag)03005 (Data Agree Flag)Word n to n+2 (Send Data)Word m to m+2 (Re
7-24H Ladder Program00000 (Write Parameter Input Bit)DIFU (013)00001MOV (021)#FF10DM0205MOV (021)#0000DM0207030000301000001ANDW (034)DM0000#FF00DM0200
7-25CMP (020)DM0205m03002ANDW (034)DM0206#00FFDM0209CMP (020)DM0208DM02090300503010Word m bit 70000225506 (Equals Flag)0300103002 030030300325506 (Equ
Chapter 8Appendices8-1 Specifications8-2 Objects8-3 CompoBus/D Communications Response Time8
8-28-1 SpecificationsItem SpecificationsModel 3G3FV-PDRT1-SINRemote I/O • Basic remote I/O: Allocated 2 input and 2 output words.• Standard remote I/O
8-38-2 ObjectsThere are eight types of object:• Identify objects (identification information): Class 01 hex• Message router objects: Class 02 hex• Dev
8-4H Object DetailsInstance Attribute Name Content SettingrangeDefault(Hex)Read Write Size00 01 Object SoftwareRevisionIndicates class 01 softwarerevi
8-5H Support Service CodeService Code No. (Hex) Service0E Get attribute singleH Object DetailsInstance Attribute Name Content SettingrangeDefault(Hex)
1-9S More than one Master Unit per PCRemote I/O can be allocated for each Slave of the Master Unit from the Configurator, so morethan one Master Unit
8-6D Allocation Information DetailsByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 1: Remote I/Oconnectionstatus1: Explicitmessageco
8-78-2-5 DeviceNet Connection Objects: Class 05 HexDeviceNet connection objects are objects related to information and operations involving CompoBus/D
8-8Instance SizeWriteReadDefault(Hex)SettingrangeContentNameAttribute01Explicitmessage09 Expected packet rate Indicates the length of theinternal proc
8-9Instance SizeWriteReadDefault(Hex)SettingrangeContentNameAttribute02RemoteI/O01 State Indicates the status of thisobject (instance).00: Does not ex
8-10Instance SizeWriteReadDefault(Hex)SettingrangeContentNameAttribute02RemoteI/O07 Produced connectionsizeIndicates the maximumnumber of bytes fortra
8-118-3 CompoBus/D Communications Response TimeThis section describes communications response time when OMRON Master and Slave Units are be-ing used.
8-12H I/O Response Time of InverterThe following shows processing time between the Inverter and the CompoBus/D CommunicationsCard.• DP-RAM processing
I-1IndexA-BAC/DC drive objects, 5-16, 5-20details, 5-20alarms, 5-34allocation areas, 1-11fixed allocation, 4-5free allocation, 4-9assembly objects, 5-
IndexI-2errorscommunications line, 6-2explicit messages, 6-5setupI/O Area Overlap, 4-6I/O Area Range Violation, 4-6special remote I/O, 6-6verification
IndexI-3Message Communications Enabled Flag, 5-11, 5-12, 7-6, 7-10Message Communications Status Flag, 5-12Message Execution Flag, 7-10message router o
1-101-3-3 CompoBus/D Communications SpecificationsItem SpecificationsCommunications protocol DeviceNetSupported connections (commu-nications)Master-Sl
IndexI-4Reset Input Bit, 7-6Reverse Input Bit, 7-2Reverse/Stop Bit, 7-2rotational speed monitor data, 5-5rotational speed reference data, 5-5, 7-2Ssca
R-1Revision HistoryA manual revision code appears as a suffix to the catalog number on the front cover of the manual.Cat. No. I525-E1-1Revision codeTh
1-11H Communications without Configurator: Fixed AllocationApplicable PC CV Series C200HX/HG/HE C200HSMaster Unit CVM1-DRM21-V1 C200HW-DRM21-V1Support
1-12Applicable PC C200HSC200HX/HG/HECV-seriesAllocation method Words are allocated to each node in the above data areas in any orderusing the Configur
Chapter 2CompoBus/DCommunications LineDesign2-1 Network Configuration Overview2-2 Network Configuration Restrictions2-3 Communications Power Supply2-4
Thank you for choosing a 3G3FV High-function General-purpose Inverter andCompoBus/D Communications Card. This manual describes the specificationsand o
2-22-1 Network Configuration OverviewThe following diagram shows the configuration of a CompoBus/D Network.CompoBus/Dcables are used.T: T-branch conne
2-32-1-2 ConnectionsH Trunk and Drop LinesThe trunk line is a cable to which Terminating Resistors are connected at the ends. Drop lines are cablestha
2-42-2 Network Configuration RestrictionsCompoBus/D communications are designed to meet a wide range of applications by providing a choiceof baud rate
2-5H Total Drop Line LengthThe total drop line length is the total sum length of all the drop lines (but not including the trunk line). Donot exceed t
2-62-3 Communications Power Supply2-3-1 Locating the Communications Power SupplyH Basic Concept• The communications power supply must be 24 VDC.• Make
2-7H FlowchartUse the flowchart below to determine the communications power supply on the trunk line. Satisfy theconditions for each drop line on page
2-81 Locating the Nodes on Both Sides of the Power SupplyPower Supply Tapor T-branch TapCommunicationspower supplyNode Node Node Node Node2 Locating t
2-9Note 3. Consider changing to Thick Cable to meet specifications if the current capacity of the ThinCable exceeds 3 A when using Thin Cable for the
2-10H Thick CableDistance (m) 0 25 50 100 150 200 250 300 350 400 450 500Max. current (A) 8.00 8.00 5.42 2.93 2.01 1.53 1.23 1.03 0.89 0.78 0.69 0.63M
2-113 Compare the values found in steps 1 and 2, above. If the first value (A) is less than the second (B),this shows that power supply specifications
!!!Notice:OMRON products are manufactured for use according to proper procedures by a qualifiedoperator and only for the purposes described in this ma
2-12Basically, in the CompoBus/D Network the permissible maximum voltage drop within the system can bespecified at 5 V for a power supply line (+V or
2-13Right Side CalculationNode 4: (40 0.015 + 1 0.005) 0.15 = 0.09075 (V)Node 5: (80 0.015 + 2 0.005) 0.25 = 0.3025 (V)Node 6: (120 0.015 +
2-142-3-5 Dual Power SuppliesBecause diodes are contained in Power Supply Taps, these taps can be used to construct a dual powersupply system in the N
2-152-4 Communications Line Noise Prevention2-4-1 Communications Line NoiseThe communications line sends and receives high-speed pulse signals, and ch
2-16Note If the cable grounded to the Inverter is not sufficient and is receiving noise interference, discon-nect the grounding cable.Shield2-4-3 Comm
2-17Suspending the Communications Power SupplyS82J power supplyS82Y-jjN (Mounting Tool)When using S82J power supplyDC power supplyInsulating material
2-182-4-5 Noise Prevention for Peripheral Devices• Install surge suppressors on devices that generate noise, particularly devices that have an inducti
Chapter 3Setup and Wiring3-1 Nomenclature and Settings3-2 Installation and Wiring3
3-23-1 Nomenclature and Settings3-1-1 Names of PartsTerminal block (TC)Node address andbaud rate settingpinsOperation indicatorsPWR indicatorMS indica
3-33-1-3 Operation IndicatorsThe CompoBus/D Communications Card has 4 operation indicators that show the status of the powerand communications as desc
!!!!!!H Installation and Wiring PrecautionsWARNING Never touch any internal parts of the Inverter. Doing so may result in electric shock.WARNING Insta
3-43-1-4 Baud Rate and Node Address SettingsIn a CompoBus/D Network, the baud rate can be set to 500 Kbps, 250 Kbps, or 125 Kbps. To manageMaster/Slav
!!!!!!3-53-2 Installation and WiringWARNING Never touch any internal parts of the Inverter. Doing so may result in electric shock.WARNING Install, rem
3-66. Press the top of the connector 2CN and check that the apexes of the triangular marks on both sidesmatch.Connector4CN for option A areaConnector2
3-73. Remove the exposed weaving and the aluminum tape from the signal and power lines. Strip thecovering from the signal and power lines to the prope
3-82. Insert the wires from underneath the terminal block.3. Tighten the terminal screws securely to a torque of 0.5 [email protected] 1. Separate the CompoBus
3-9D DCN1-1C T-branch Tap* Use for trunk line oflongest drop line.D DCN1-3C T-branch Tap* Use for trunk line oflongest drop line.D T-branch Tap Connec
3-10H Connecting Terminating ResistorsTerminating resistors must be connected at each end of the trunk line. Use the methods described hereto connect
Chapter 4CompoBus/D SystemStartup4-1 SYSMAC Word Allocations and Scan List4-2 SYSDRIVE 3G3FV Settings4-3 Startup Procedure4
4-24-1 SYSMAC Word Allocations and Scan ListIn a CompoBus/D Network, remote I/O and message communications can be used simultaneously.This section des
4-3• Slaves that require two words can be allocated two words using only one node address so that the nextnode addresses can be set for another Slave.
Table of ContentsChapter 1. Functions and System Configuration 1-1. . . . . . . . . . . . . . . . . 1-1 Functions 1-2. . . . . . . . . . . . . . . . .
4-4• Slave remote I/O allocations providing the number of I/O words allocated to and the node address setfor each Slave.• Communications parameters pr
4-5H Using Scan ListsD Enabling/Disabling a Scan ListTo enable a scan list, turn ON the Enable Scan List software switch or use the Configurator. To d
4-6NodeSYSMAC Programmable ControllersaddressCV-series PCs C200HX/HG/HE PCs C200HS PCsOutput area(CIO 1900 toCIO 1963)Input area(CIO 2000 toCIO 2063)O
4-7D Verification Error: Slave I/O Size DiffersA verification error (Slave I/O Size Differs) will occur and it will not be possible to start CompoBus/
4-82. Set the initial settings for the Slaves:Node address (DIP switch)Baud rate (DIP switch)Etc.3. Mount the Master Unit and wire the Network.For CV-
4-94-1-4 Free AllocationsH Allocation Areas and Maximum Words for Different PCsWhen free allocations are used, the remote I/O areas consist of input b
4-10H Free Allocation Restrictions• Each node address can be set only once in the output blocks and once in the input blocks.The same node ad-dress ca
4-11H Example of Free AllocationsOutput areaCIO 1950CIO 1951CIO 1952CIO 1953CIO 1954CIO 2000Allocated (01)Not usedNot usedAllocated (12)Allocated (02)
4-128. Connect a Configurator to the Network.9. Turn ON the power supply to all nodes.10. Switch the PC to PROGRAM mode.11. Get the device list and cr
4-134-2 SYSDRIVE 3G3FV SettingsSet the parameters according to the applications of the Inverter for CompoBus/D communications. Theshaded part in the f
Table of ContentsChapter 5. CompoBus/D Communications Card Operations 5-1. . . . . . . 5-1 Remote I/O 5-2. . . . . . . . . . . . . . . . . . . . . . .
4-144-2-3 CompoBus/D Communications SettingsThe parameters below have been added for functions that are exclusive to CompoBus/D communica-tions. Set t
4-154-2-4 Frequency Reference Settings and Display UnitsThe parameters for units of frequency (speed) data used in CompoBus/D communications are set w
4-164-3 Startup ProcedureThe CompoBus/D communications system can be started from any of the nodes on the Network. Thefollowing procedure gives the st
Chapter 5CompoBus/DCommunications CardOperations5-1 Remote I/O5-2 Message Communications (DeviceNet Explicit Messages)5-3 Switching Remote I/O Operati
!5-2Caution Be careful when changing settings. Not doing so may result in injury or product dam-age.5-1 Remote I/OThere are two types of CompoBus/D co
5-35-1-1 Standard Remote I/O (Initial Setting)The type of remote I/O operation pre-set as the initial setting for the Inverter’s CompoBus/D Commu-nica
5-4H Words Allocated to SYSDRIVE 3G3FV-series InvertersA SYSDRIVE 3G3FV-series Inverter is allocated a total of four SYSMAC I/O words (two input and t
5-5Note 2. Control From Net shows the input status of word n, bit 5 (Net Control) for CompoBus/D com-munications.Note 3. The Reference From Net and Co
5-65-1-2 Types of Remote I/O OperationThere are three types of CompoBus/D Communications Card remote I/O operation:• Basic remote I/O: Remote I/O oper
5-7D Inputs (3G3FV to SYSMAC PC) Instance ID: 71 Dec (47 Hex)Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0Wd mRightmost 0 AtReferenceRef
Chapter 1Functions and SystemConfiguration1-1 Functions1-2 CompoBus/D Features1-3 CompoBus/D System Configuration1
5-85-2 Message Communications (DeviceNet Explicit Messages)There are two types of CompoBus/D communications: Remote I/O and message communications. Th
5-9Note Message communications are supported by CV-series and C200HX/HG/HE PCs, but not byC200HS PCs.H Overview of Explicit MessagesExplicit messages
5-10D C: Control CodeThe control code is set as shown below for CompoBus/D Master Units.Response setting:ON: No response.OFF: Response required.Must b
5-11H Message TimingThe Message Communications Enabled Flag must be used as an execution condition for the Masterwhen IOWR is used. Be sure this flag
5-12H Timing of Message Response ReadingResponses are read when the Message Communications Enabled Flag turns ON in the next cycle. TheMessage Communi
5-135-2-3 SYSMAC CV-series Message TransmissionH Using CMND(194)With CV-series PCs, CMND(194) is used to send explicit messages. To send an explicit m
5-14D C: Beginning Control Code WordSpecify the beginning word address of the area for storing the required control codes for message com-munications.
5-15H Communications FlagsType NameAddressContentWord BitSYSMACPC flagsNetwork CommunicationsEnabled FlagA502 7: Port 76: Port 65: Port 54: Port 43: P
5-16H Response FormatD Normal ResponseCommand code(FINS command for PC)Destination node address32 bytes max.Completion codeNumber of bytes transmitted
5-17H Object DetailsInstance Attribute Name Content Setting range Default Read Write Size00 01 Object SoftwareRevisionIndicates class 28 softwarerevis
1-21-1 FunctionsThe 3G3FV-PDRT1-SIN CompoBus/D Communications Card is a dedicated communications interfacecard that makes it possible for the SYSDRIVE
5-18H Object DetailsInstance Attribute Name Content SettingrangeDefault Read Write Size00 01 Object SoftwareRevisionIndicates class 29 softwarerevisio
5-19Note 2. A DeviceNet Fault mode cannot be set from communications. The Inverter will stop when acommunications fault is detected. In versions S1042
5-205-2-7 AC/DC Drive Objects: Class 2A HexAC/DC drive objects are assigned to command-related functions for drive devices such as Invertersand Servom
5-21Instance SizeWriteReadDefaultSettingrangeContentNameAttribute0109 Current Actual Can be referenced in hexadecimal with theoutput current monitor (
5-22Instance SizeWriteReadDefaultSettingrangeContentNameAttribute011A Power scale Power data unit selection can be set andread. The power data unit va
5-23Note With frequency, the speed scale has no effect.Example 3: Finding the communications data for setting a one-minute acceleration time with the
5-245-3 Switching Remote I/O OperationTo use remote I/O operations other than the standard remote I/O operation it is necessary to switch theremote I/
5-255. Set up the Master Unit and 3G3FV Inverter connection by turning ON their power. The remote I/Oconnection will then start up with the specified
5-26Note For details on using message communications, refer to 5-2 Message Communications (Device-Net Explicit Messages and the operation manual for t
5-275-4 Special Remote I/O OperationThere are three kinds of CompoBus/D remote I/O operation: Basic remote I/O, standard remote I/O (thedefault settin
1-3Note 2. The SYSMAC CV Series includes the CV1000, CV2000, and CVM1 Programmable Control-lers. SYSMAC C200HS PCs support only remote I/O communicati
5-28H Setting Data for Operations and Parameter ConstantsRead data and write data to be set for operations and parameters are calculated as shown belo
5-29Note 1. Unless an enter command is transmitted, data will not be enabled and the Inverter may notstart.Note 2. The enter command requires a parame
5-30H Handling IllustrationFunction coderegister numberProcessing contents10 hex0001 hex10 hex0000 hex03 hex0021 hex03 hex0010 hexFrequency reference
5-31D Inverter Run Commands: Register Number 0000 HexBit Content0 Forward/stop (1: Forward operation)1 Reverse/stop (1: Reverse operation)2 Multi-func
5-325-4-4 Inverter Monitoring FunctionsAll Inverter monitoring can be accessed. To read Inverter status, fault monitoring, alarm monitoring, I/Ostatus
5-33D Fault 1: Register Number 0014 HexBit Display Content0 PUF Fuse open1 UV1 Undervoltage (main)2 UV2 Undervoltage (CTL)3 UV3 Undervoltage (MC)4 SC
5-34D CPF Error 1: Register Number 0017Bit Display Content0 ---Not used.1 ---2 CPF02 Baseblock circuit error3 CPF03 EEPROM error4 CPF04 Internal A/D e
5-35H Inverter Monitoring: U1–jjRegisternumberMonitornumberMonitored item Output unit Read Write0020 U1-01 Frequency reference Set in o1-03 Yes No0021
5-36D Output Terminal Status: Register Number 002A HexBit Content0 1: Terminal 9 and 10 short1 1: Terminal 25 and 27 short2 1: Terminal 26 and 27 shor
5-37H Inverter Monitoring: U2–jj, U3–jjRegisternumberMonitornumberMonitored item Output unit Read Write0080 U2-01 Current fault (Refer to table below.
Commenti su questo manuale